Tomgenerator TGC900 – TGC1000S (50 Hz) powered by Cummins
The above ratings represent the generating set capability guaranteed within ±3% at the reference conditions equivalent to those specified in ISO 8528/1 standard.
1. The applicable voltage range is 380V to 415V for 50Hz applications. For other voltages, please consult factory.
2. This generating set is of fixed speed of 1500 rpm.
3. CT900 is the prime power rating of the generating set is where a variable load and unlimited hour usage are applied with an average load factor of 80% of the prime rating over each 24-hour period. Noting that a 10% overload is permitted for 1 hour in every 12-hour operation.
4. CT1000S is the standby power rating of the generating set is where a variable load limited to an annual usage up to 500 hours is applied, with 300 hours of which may be continuous running. Noting that no overload is permitted.
Engine Technical Data
Make & Model
CUMMINS KTA38-G3
Cylinders & Arrangement
12;60 Vee
Bore & Stroke (mm)
159×159
Induction system
Turbo Charged & Aftercooled
Combustion
Direct injection
Cycle
4 stroke
Compression ratio
13:9:1 1
Cooling System
Water cooled
Displacement
37.8 liters
Lube oil capacity
140 liters Max
Coolant capacity
218.5 liters
Standard governor
Electronic
Engine Speed
1500 rpm
Consumption @ 100% Load (L/H)
198
Consumption @ 75% Load (L/H)
151
Consumption @ 50% Load (L/H)
104
Consumption @ 25% Load (L/H)
54
Radiator Cooling Air Flow (m3/s)
18.7 Emissions regulations
For non-regulated territories
Exhaust temperature ᵒC (max)
524
Max exhaust gas flow (m3/min)
238
Max. allowed back pressure (kPa)
10..0
The above performance data are valid as per the following specs:
• Diesel Fuel is according to BS2869 Class A2 or equivalent.
• Lubricating oil is according to Grade SAE 15W-40 API CI4.
• The coolant should be 50% antifreeze and 50% fresh water.Alternator Technical Data
Make & Model
Leroy Somer TAL049E
Frequency / No. of poles
50Hz / 4P
Ingress protection
IP23
Insulation class
H
Terminals (Optional)
6 (12)
Excitation system
SHUNT
Winding pitch
2/3
AVR model
R150
Overspeed
2250 R.P.M.
Voltage regulation
± 1 %
Coolant air flow
1.0 m3/s